Faults and Alarms

List of Faults and Alarms

3.2
List of Faults and Alarms
Product: SINAMICS G120, Version: 4402100, Language: eng,
Objects: CU230P-2 CAN, CU230P-2 DP, CU230P-2 HVAC
F01000
Internal software error
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- evaluate fault buffer (r0945).
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
- replace the Control Unit.
F01001
FloatingPoint exception
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An exception occurred during an operation with the FloatingPoint data type.
The error may be caused by the base system or an OA application (e.g., FBLOCKS, DCC).
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Note:
Refer to r9999 for further information about this fault.
r9999[0]: Fault number.
r9999[1]: Program counter at the time when the exception occurred.
r9999[2]: Cause of the FloatingPoint exception.
Bit 0 = 1: Operation invalid
Bit 1 = 1: Division by zero
Bit 2 = 1: Overflow
Bit 3 = 1: Underflow
Bit 4 = 1: Imprecise result
Remedy:
- carry out a POWER ON (power off/on) for all components.
- check configuration and signals of the blocks in FBLOCKS.
- check configuration and signals of DCC charts.
- upgrade firmware to later version.
- contact the Hotline.
F01002
Internal software error
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
An internal software error has occurred.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
F01003
Acknowledgement delay when accessing the memory
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A memory area was accessed that does not return a "READY".
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- contact the Hotline.
3-658
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
© Siemens AG 2011 All Rights Reserved