Parameters
List of Parameters
p1802[0...n]
Modulator mode / Modulator mode
PM230
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the modulator mode.
Value:
0:
2:
3:
4:
10:
Dependency:
If a sine-wave filter is parameterized as output filter (p0230 = 3, 4), then only space vector modulation without over-
control can be selected as modulation type (p1802 = 3). This is not valid for the power units PM260. p1802 = 10 can
only be set for the PM230 and PM240 power units.
Refer to: p0230, p0500
Note:
When modulation modes are enabled that could lead to overmodulation (p1802 = 0, 2, 10), the modulation depth
must be limited using p1803 (pre-assignment, p1803 = 98%). The higher the overmodulation, the greater the cur-
rent ripple and torque ripple. With p1802 = 10, the modulation depth limit is automatically reduced to 100% in the
critical output frequency range (over approx. 57 Hz).
When changing p1802[x], the values for all of the other existing indices are also changed.
p1802[0...n]
Modulator mode / Modulator mode
PM240
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the modulator mode.
Value:
0:
2:
3:
4:
10:
Dependency:
If a sine-wave filter is parameterized as output filter (p0230 = 3, 4), then only space vector modulation without over-
control can be selected as modulation type (p1802 = 3). This is not valid for the power units PM260. p1802 = 10 can
only be set for the PM230 and PM240 power units.
Refer to: p0230, p0500
Note:
When modulation modes are enabled that could lead to overmodulation (p1802 = 0, 2,10), the modulation depth
must be limited using p1803 (default p1803 < 100 %). The higher the overmodulation, the greater the current ripple
and torque ripple.
When changing p1802[x], the values for all of the other existing indices are also changed.
1-228
Automatic changeover SVM/FLB
Space vector modulation (SVM)
SVM without overcontrol
SVM/FLB without overcontrol
SVM/FLB with modulation depth reduction
Automatic changeover SVM/FLB
Space vector modulation (SVM)
SVM without overcontrol
SVM/FLB without overcontrol
SVM/FLB with modulation depth reduction
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
10
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
10
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: Integer16
Data set: DDS, p0180
Factory setting
10
Data type: Integer16
Data set: DDS, p0180
Factory setting
0
© Siemens AG 2011 All Rights Reserved