Parameters
List of Parameters
p8430[0...6]
RTC DTC3 weekday of activation / RTC DTC3 day act
Access level: 3
Can be changed: T
Units group: -
Min
0000 bin
Description:
Sets the weekday on which timer 3 is activated (DTC3).
The switch-on/off time is set in p8431/p8432 and the result displayed via binector output r8433.
Value:
0:
1:
Index:
[0] = Monday
[1] = Tuesday
[2] = Wednesday
[3] = Thursday
[4] = Friday
[5] = Saturday
[6] = Sunday
Dependency:
Refer to: p8409, p8431, p8432, r8433
Notice:
This parameter can only be changed when p8409 = 0.
Note:
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8431[0...1]
RTC DTC3 switch-on time / RTC DTC3 t_ON
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the switch on time in hours and minutes for timer 3 (DTC3).
BO: r8433 = 1 signal:
The condition for the set weekday (p8430) and switch-on time has been fulfilled.
Index:
[0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency:
Refer to: p8409, p8430, r8433
Notice:
This parameter can only be changed when p8409 = 0.
Note:
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8432[0...1]
RTC DTC3 off time / RTC DTC3 t_OFF
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the switch off time in hours and minutes for timer 3 (DTC3).
BO: r8433 = 0 signal:
The condition for the set weekday (p8430) and switch-off time has been fulfilled.
Index:
[0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency:
Refer to: p8409, p8430, r8433
Notice:
This parameter can only be changed when p8409 = 0.
Note:
DTC: Digital Time Clock (timer)
RTC: Real-time clock
1-344
Weekday de-activated
Weekday activated
Calculated: -
Scaling: -
Unit selection: -
Max
0001 bin
Calculated: -
Scaling: -
Unit selection: -
Max
59
Calculated: -
Scaling: -
Unit selection: -
Max
59
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: Integer16
Data set: -
Factory setting
0000 bin
Data type: Unsigned16
Data set: -
Factory setting
0
Data type: Unsigned16
Data set: -
Factory setting
0
© Siemens AG 2011 All Rights Reserved