Parameters
List of Parameters
p11274
Free tec_ctrl 2 differentiation time constant / Ftec2 D comp T
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the time constant for the differentiation (D component) of the free technology controller 2.
Note:
Value = 0: Differentiation is de-activated.
p11280
Free tec_ctrl 2 proportional gain / Ftec2 Kp
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000
Description:
Sets the proportional gain (P component) of the free technology controller 2.
Note:
Value = 0: The proportional gain is de-activated.
p11285
Free tec_ctrl 2 integral time / Ftec2 Tn
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the integral time (I component, integrating time constant) of the free technology controller 2.
Note:
Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
p11291
CO: Free tec_ctrl 2 limit maximum / Ftec2 lim max
Access level: 3
Can be changed: U, T
Units group: -
Min
-200.00 [%]
Description:
Sets the maximum limit of the free technology controller 2.
Dependency:
Refer to: p11292
Note:
The maximum limit must always be greater than the minimum limit (p11291 > p11292).
p11292
CO: Free tec_ctrl 2 limit minimum / Ftec2 lim min
Access level: 3
Can be changed: U, T
Units group: -
Min
-200.00 [%]
Description:
Sets the minimum limit of the free technology controller 2.
Dependency:
Refer to: p11291
Note:
The maximum limit must always be greater than the minimum limit (p11291 > p11292).
1-394
Calculated: -
Scaling: -
Unit selection: -
Max
60.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.000
Calculated: -
Scaling: -
Unit selection: -
Max
10000.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
0.000 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
1.000
Data type: FloatingPoint32
Data set: -
Factory setting
30.000 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [%]
Data type: FloatingPoint32
Data set: -
Factory setting
0.00 [%]
© Siemens AG 2011 All Rights Reserved