Siemens SINAMICS G120 Manual page 27

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

r0046.0...31
CO/BO: Missing enable sig / Missing enable sig
Access level: 1
Can be changed: -
Units group: -
Min
-
Description:
Displays missing enable signals that are preventing the closed-loop drive control from being commissioned.
Bit field:
Bit
Signal name
00
OFF1 enable missing
01
OFF2 enable missing
02
OFF3 enable missing
03
Operation enable missing
04
DC braking enable missing
10
Ramp-function generator enable missing
11
Ramp-function generator start missing
12
Setpoint enable missing
16
OFF1 enable internal missing
17
OFF2 enable internal missing
18
OFF3 enable internal missing
19
Pulse enable internal missing
20
DC braking internal enable missing
21
PU enab. missing
25
Function bypass active
26
Drive inactive or not operational
27
De-magnetizing not completed
30
Speed controller inhibited
31
Jog setpoint active
Dependency:
Refer to: r0002
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
List of Parameters
Data type: Unsigned32
Data set: -
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1-27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2