p1042[0...n]
CI: Motorized potentiometer automatic setpoint / Mop auto setpoint
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the setpoint of the motorized potentiometer in the automatic mode.
Dependency:
Refer to: p1041
p1043[0...n]
BI: Motorized potentiometer accept setting value / MotP acc set val
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to accept the setting value for the motorized potentiometer.
Dependency:
Refer to: p1044
Note:
The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
p1044[0...n]
CI: Motorized potentiometer setting value / Mop set val
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the setting value for the motorized potentiometer.
Dependency:
Refer to: p1043
Note:
The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
r1045
CO: Mot. potentiometer speed setp. in front of ramp-fct. gen. / Mop n_set bef RFG
Access level: 3
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator.
p1047[0...n]
Motorized potentiometer ramp-up time / Mop ramp-up time
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from zero up to the speed/velocity limit (p1082) within this time (if no initial rounding-off has
been activated).
Dependency:
Refer to: p1030, p1048, p1082
Note:
When the initial rounding-off is activated (p1030.2) the ramp-up time is correspondingly extended.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.000 [s]
Parameters
List of Parameters
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: -
Factory setting
- [rpm]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
10.000 [s]
1-133