p1340[0...n]
I_max frequency controller proportional gain / I_max_ctrl Kp
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000
Description:
Sets the proportional gain of the I_max voltage controller.
The I_max controller reduces the drive converter output current if the maximum current (r0067) is exceeded.
In the U/f operating modes (p1300) for the I_max control, one controller is used that acts on the output frequency
and one controller that acts on the output voltage. The frequency controller reduces the current by decreasing the
converter output frequency. The frequency is reduced down to a minimum value (equaling twice rated slip). If the
overcurrent condition cannot be successfully resolved using this measure, then the drive converter output voltage is
reduced using the I_max voltage controller. Once the overcurrent condition has been resolved, the drive is acceler-
ated along the ramp set in p1120 (ramp-up time).
Dependency:
In the U/f modes (p1300) for textile applications and for external voltage setpoints, only the I_max voltage controller
is used.
Notice:
When de-activating the I_max controller, the following must be carefully observed:
When the maximum current (r0067) is exceeded, the output current is no longer reduced, however, overcurrent
alarm messages are generated. The drive is shut down if the overcurrent limit (r0209) is exceeded.
Note:
The I_max limiting controller becomes ineffective if the ramp-function generator is de-activated with p1122 = 1.
p1341 = 0: I_max frequency controller de-activated and I_max voltage controller activated over the complete speed
range.
p1341[0...n]
I_max frequency controller integral time / I_max_ctrl Tn
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the integral time for the I_max frequency controller.
Dependency:
Refer to: p1340
Note:
When p1341 = 0, the current limiting controller influencing the frequency is de-activated and only the current limiting
controller influencing the output voltage remains active (p1345, p1346).
In the case of power units with regenerative feedback (PM250, PM260), current limitation control for a regenerative
load is always implemented by influencing the frequency. This current limiting function is de-activated with p1340 =
p1341 = 0.
r1343
CO: I_max controller frequency output / I_max_ctrl f_outp
Access level: 3
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Displays the effective frequency limit.
Dependency:
Refer to: p1340
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
0.500
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
50.000 [s]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.000
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.300 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
- [rpm]
1-187