Siemens SINAMICS G120 Manual page 222

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Parameters
List of Parameters
p1758[0...n]
Motor model changeover delay time closed/open-loop control / MotMod t cl_op
Access level: 3
Can be changed: U, T
Units group: -
Min
100 [ms]
Description:
Sets the minimum time for falling below the changeover speed when changing from closed-loop controlled opera-
tion to open-loop controlled operation.
Dependency:
Refer to: p1755, p1756
p1759[0...n]
Motor model changeover delay time open/closed-loop control / MotMod t op_cl
Access level: 3
Can be changed: U, T
Units group: -
Min
0 [ms]
Description:
Sets the minimum time for exceeding the changeover speed when changing from open-loop controlled operation to
closed-loop controlled operation.
Dependency:
Refer to: p1755, p1756
Note:
When p1759 = 2000 ms, the delay time becomes ineffective and the model changeover is determined by the output
frequency only.
r1762[0...1]
Motor model deviation component 1 / MotMod dev comp 1
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Induction motor (ASM):
Displays the referred imaginary system deviation for the adaptation circuit of the motor model.
Permanent-magnet synchronous motor (PESM):
Displays the system deviation for speed adaptation.
r1762.0: Angular deviation [rad-el] of the estimated EMF.
r1762.1: Angular deviation [electr. deg.] of the low-level signal response for pulse technique.
Index:
[0] = Deviation Model1
[1] = Deviation Model2
r1763
Motor model deviation component 2 / MotMod dev comp 2
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Induction motor (ASM):
Displays the referred real system deviation for the adaptation circuit of the motor model.
Permanent-magnet synchronous motor (PESM):
Not used.
1-222
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
2000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
500 [ms]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0 [ms]
Data type: FloatingPoint32
Data set: -
Factory setting
-
Data type: FloatingPoint32
Data set: -
Factory setting
-
© Siemens AG 2011 All Rights Reserved