Siemens SINAMICS G120 Manual page 47

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

p0230
Drive filter type, motor side / Drv filt type mot
Access level: 1
Can be changed: C(1, 2)
Units group: -
Min
0
Description:
Sets the type of the filter at the motor side.
Value:
0:
1:
2:
3:
4:
Dependency:
The following parameters are influenced using p0230:
p0230 = 1:
--> p0233 (power unit, motor reactor) = filter inductance
p0230 = 3:
--> p0233 (power unit, motor reactor) = filter inductance
--> p0234 (power unit sine-wave filter capacitance) = filter capacitance
--> p0290 (power unit overload response) = inhibit pulse frequency reduction
--> p1082 (maximum speed) = Fmax filter / pole pair number
--> p1800 (pulse frequency) >= nominal pulse frequency of the filter
--> p1802 (modulator modes) = space vector modulation without overcontrol
p0230 = 4:
--> p0290 (power unit overload response) = inhibit pulse frequency reduction
--> p1802 (modulator modes) = space vector modulation without overcontrol
The user must set the following parameters according to the data sheet of the sine-wave filter and also the user
must check whether they are permitted.
--> p0233 (power unit, motor reactor) = filter inductance
--> p0234 (power unit sine-wave filter capacitance) = filter capacitance
--> p1082 (maximum speed) = Fmax filter / pole pair number
--> p1800 (pulse frequency) >= nominal pulse frequency of the filter
Refer to: p0233, p0234, p0290, p1082, p1800, p1802
Note:
If the power unit (e.g. PM260) is equipped with an internal sine-wave filter, the parameter cannot be changed.
if a filter type cannot be selected, then this filter type is not permitted for the Motor Module.
p0230 = 1:
Power units with output reactor are limited to output frequencies of 150 Hz.
p0230 = 3:
Power units with sine-wave filter are limited to output frequencies of 200 Hz.
r0231[0...1]
Power cable length, maximum / Cable length max
Access level: 3
Can be changed: -
Units group: -
Min
- [m]
Description:
Displays the maximum permissible cable lengths between the drive unit and motor.
Index:
[0] = Unshielded
[1] = Shielded
Note:
The display value is used to provide information for service and maintenance.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
No filter
Motor reactor
dv/dt filter
Sine-wave filter, Siemens
Sine-wave filter, third-party
Calculated: -
Scaling: -
Unit selection: -
Max
4
Calculated: -
Scaling: -
Unit selection: -
Max
- [m]
Parameters
List of Parameters
Data type: Integer16
Data set: -
Factory setting
0
Data type: Unsigned16
Data set: -
Factory setting
- [m]
1-47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2

Table of Contents