r2349.0...12
CO/BO: Technology controller status word / Tec_ctrl status
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the status word of the technology controller.
Bit field:
Bit
Signal name
00
Technology controller de-activated
01
Technology controller limited
02
Technology controller, motorized potentiom-
eter limited max.
03
Technology controller, motorized potentiom-
eter limited min.
04
Technology controller speed setpoint total in
setpoint channel
05
Technology controller RFG bypassed in the
setpoint channel
06
Technology controller starting value at the
current limit
08
Technology controller actual value at the
minimum
09
Technology controller actual value at the
maximum
10
Technology controller output at the mini-
mum
11
Technology controller output at the maxi-
mum
12
Fault response active
p2370[0...n]
Staging enable / Staging enab
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the signal source to switch in/switch out the "staging" function.
1 signal: The function is switched in.
Value:
0:
1:
Note:
The technology controller must be activated (p2200) and configured (p2251 = 0) in order to use the "staging" func-
tion.
Negative speed setpoints should be excluded.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Motor staging disabled
Motor staging enabled
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
1
Parameters
List of Parameters
Data type: Unsigned32
Data set: -
Factory setting
-
0 signal
No
No
No
No
No
No
Yes
No
No
No
No
No
Data type: Integer16
Data set: DDS, p0180
Factory setting
0
FP
-
-
-
-
-
-
-
-
-
-
-
-
1-311