Faults and Alarms
List of Faults and Alarms
A03520 (F, N)
CU: Temperature sensor fault
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
It is expected that an Ni1000 temperature sensor (p0756[2...3] = 6) or PT1000 p0756[2...3] = 7 is connected via the
analog input.
Alarm value (r2124, interpret decimal):
33: Analog input 2 (AI2) wire breakage or sensor not connected.
34: Analog input 2 (AI2) measured resistance too low (short circuit).
49: Analog input 3 (AI3) wire breakage or sensor not connected.
50: Analog input 3 (AI3) measured resistance too low (short circuit).
See also: p0756 (CU analog inputs type)
Remedy:
- make sure that the sensor is connected correctly.
- check the sensor for correct function and if required, replace.
- change over the analog input to type "no sensor connected" (p0756 = 8).
A05000 (N)
Power unit: Overtemperature heat sink AC inverter
Reaction:
NONE
Acknowledge:
NONE
Cause:
The alarm threshold for overtemperature at the inverter heat sink has been reached. The response is set using
p0290.
If the temperature of the heat sink increases by an additional 5 K, then fault F30004 is initiated.
Remedy:
Check the following:
- is the ambient temperature within the defined limit values?
- have the load conditions and the load duty cycle been appropriately dimensioned?
- has the cooling failed?
A05001 (N)
Power unit: Overtemperature depletion layer chip
Reaction:
NONE
Acknowledge:
NONE
Cause:
Alarm threshold for overtemperature of the power semiconductor in the AC converter has been reached.
Note:
- The response is set using p0290.
- If the depletion layer temperature increases by an additional 15 K, then fault F30025 is triggered.
Remedy:
Check the following:
- is the ambient temperature within the defined limit values?
- have the load conditions and the load duty cycle been appropriately dimensioned?
- has the cooling failed?
- pulse frequency too high?
See also: r0037 (Power unit temperatures), p0290 (Power unit overload response)
A05002 (N)
Power unit: Air intake overtemperature
Reaction:
NONE
Acknowledge:
NONE
Cause:
For chassis power units, the following applies:
The alarm threshold for the air intake overtemperature has been reached. For air-cooled power units, the threshold
is 42 °C (hysteresis 2 K). The response is set using p0290.
If the air intake temperature increases by an additional 13 K, then fault F30035 is output.
Remedy:
Check the following:
- is the ambient temperature within the defined limit values?
- has the fan failed? Check the direction of rotation.
3-674
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
© Siemens AG 2011 All Rights Reserved