Parameters
List of Parameters
p0015
Macro drive unit / Macro drv unit
CU230P-2 CAN
Access level: 1
CU230P-2 HVAC
Can be changed: C, C(1)
Units group: -
Min
0
Description:
Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0015 = 6 --> the macro file PM000006.ACX is run.
Dependency:
Refer to: p0700, p1000, p1500, r8570
Caution:
When executing a specific macro, the corresponding programmed settings are made and become active.
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
The macros in the specified directory are displayed in r8570. r8570 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
The parameter is not influenced by setting the factory setting.
p0015
Macro drive unit / Macro drv unit
CU230P-2 DP
Access level: 1
Can be changed: C, C(1)
Units group: -
Min
0
Description:
Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0015 = 6 --> the macro file PM000006.ACX is run.
Dependency:
Refer to: p0700, p1000, p1500, r8570
Caution:
When executing a specific macro, the corresponding programmed settings are made and become active.
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
The macros in the specified directory are displayed in r8570. r8570 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
The parameter is not influenced by setting the factory setting.
r0018
Control Unit Firmware-Version / CU FW version
Access level: 3
Can be changed: -
Units group: -
Min
0
Description:
Displays the firmware version of the Control Unit.
Dependency:
Refer to: r0197, r0198
Note:
Example:
The value 1010100 should be interpreted as V01.01.01.00.
1-20
Calculated: -
Scaling: -
Unit selection: -
Max
999999
Calculated: -
Scaling: -
Unit selection: -
Max
999999
Calculated: -
Scaling: -
Unit selection: -
Max
4294967295
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: Unsigned32
Data set: -
Factory setting
12
Data type: Unsigned32
Data set: -
Factory setting
7
Data type: Unsigned32
Data set: -
Factory setting
-