p0596
Reference quantity, technological units / Ref tech units
Access level: 1
Can be changed: T
Units group: -
Min
0.01
Description:
Sets the reference quantity for the technological units. When changing over using changeover parameter 595 to
absolute units, all of the parameters involved refer to the reference quantity.
Dependency:
Refer to: p0595
p0601[0...n]
Motor temperature sensor type / Mot_temp_sens type
Access level: 2
Can be changed: C(3), U, T
Units group: -
Min
0
Description:
Sets the sensor type for the motor temperature monitoring.
Value:
0:
1:
2:
4:
Dependency:
The thermal motor model is only calculated for p0612.1 = 1.
Caution:
If, for a selected KTY temperature sensor (p0601 = 2), the motor temperature sensor is not connected but another
encoder, then the temperature adaptation of the motor resistances must be switched out (p0620 = 0). Otherwise, in
controlled-loop operation, torque errors will occur that will mean that the drive will not be able to be stopped.
Note:
PTC thermistor (p0601 = 1): Tripping resistance = 1650 Ohm.
p0604[0...n]
Motor temperature alarm threshold / Mot_temp al thr
Access level: 2
Can be changed: C(3), U, T
Units group: 21_1
Min
0.0 [°C]
Description:
Sets the alarm threshold for monitoring the motor temperature.
Dependency:
Refer to: p0606
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis for canceling the alarm is 2 Kelvin.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
No sensor
PTC alarm & timer
KTY84
Bimetallic NC contact alarm & timer
Calculated: -
Scaling: -
Unit selection: -
Max
340.28235E36
Calculated: -
Scaling: -
Unit selection: -
Max
4
Calculated: -
Scaling: -
Unit selection: p0505
Max
240.0 [°C]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
1.00
Data type: Integer16
Data set: MDS
Factory setting
0
Data type: FloatingPoint32
Data set: MDS
Factory setting
130.0 [°C]