Parameters
List of Parameters
p11257
Free tec_ctrl 2 setpoint ramp-up time / Ftec2 setp t_r-up
Access level: 2
Can be changed: U, T
Units group: -
Min
0.00 [s]
Description:
Sets the ramp-up time for the free technology controller 2.
Dependency:
Refer to: p11258
Note:
The ramp-up time is referred to 100 %.
p11258
Free tec_ctrl 2 setpoint ramp-down time / Ftec2 setp t_r-dn
Access level: 2
Can be changed: U, T
Units group: -
Min
0.00 [s]
Description:
Sets the ramp-down time of the free technology controller 2.
Dependency:
Refer to: p11257
Note:
The ramp-down time is referred to 100 %.
r11260
CO: Free tec_ctrl 2 setpoint after ramp-function generator / Ftec2 setp aft RFG
Access level: 2
Can be changed: -
Units group: 9_4
Min
- [%]
Description:
Display and connector output for the setpoint after the ramp-function generator of the free technology controller 2.
p11264
CI: Free tec_ctrl 2 actual value signal source / Ftec2 act v s_s
Access level: 2
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the actual value of the free technology controller 2.
p11265
Free tec_ctrl 2 actual value smoothing time constant / Ftec2 act v T
Access level: 2
Can be changed: U, T
Units group: -
Min
0.00 [s]
Description:
Sets the smoothing time constant (PT1) for the actual value of the free technology controller 2.
1-392
Calculated: -
Scaling: -
Unit selection: -
Max
650.00 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
650.00 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p11226
Max
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
60.00 [s]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
1.00 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
1.00 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
Data type: U32 / FloatingPoint32
Data set: -
Factory setting
0
Data type: FloatingPoint32
Data set: -
Factory setting
0.00 [s]
© Siemens AG 2011 All Rights Reserved