Siemens SINAMICS G120 Manual page 340

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Parameters
List of Parameters
p8405
Activate/de-activate RTC alarm A01098 / RTC A01098 act
Access level: 3
Can be changed: T
Units group: -
Min
0000 bin
Description:
Sets whether the real-time clock outputs an alarm if the time is not synchronized (e.g. if the power supply was
switched off for an extended period).
Value:
0:
1:
Dependency:
Refer to: A01098
Note:
RTC: Real-time clock
p8409
RTC DTC activation / RTC DTC act
Access level: 3
Can be changed: U, T
Units group: -
Min
0000 bin
Description:
Sets the activation/de-activation of the parameters for timers DTC1, DTC2, DTC3.
For p8409 = 0, the following applies:
DTC1 parameters p8410, p8411, p8412 are inactive and can be set. Binector output r8413.0 = 0.
DTC2 parameters p8420, p8421, p8422 are inactive and can be set. Binector output r8423.0 = 0.
DTC3 parameters p8430, p8431, p8432 are inactive and can be set. Binector output r8433.0 = 0.
For p8409 = 1, the following applies:
DTC1 parameters p8410, p8411, p8412 are active and cannot be set. Binector outputs r8413 are active.
DTC2 parameters p8420, p8421, p8422 are active and cannot be set. Binector outputs r8423 are active.
DTC3 parameters p8430, p8431, p8432 are active and cannot be set. Binector outputs r8433 are active.
Value:
0:
1:
Dependency:
Refer to: p8410, p8411, p8412, r8413, p8420, p8421, p8422, r8423, p8430, p8431, p8432, r8433
Note:
DTC: Digital Time Clock (timer)
RTC: Real-time clock
1-340
Alarm A01098 de-activated
Alarm A01098 activated
DTC inactive and can be set
DTC active and cannot be set
Calculated: -
Scaling: -
Unit selection: -
Max
0001 bin
Calculated: -
Scaling: -
Unit selection: -
Max
0001 bin
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: Integer16
Data set: -
Factory setting
0001 bin
Data type: Integer16
Data set: -
Factory setting
0001 bin
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2

Table of Contents