Parameters
List of Parameters
p3883
BI: ESM direc. rot. / ESM direc. rot.
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Selects the signal source for the direction of rotation during emergency operation (ESM).
0 = The direction of rotation of the setpoint parameterized for emergency operation is maintained.
1 = The direction of rotation of the setpoint parameterized for emergency operation is reversed.
Warning:
The direction reversal is not taken into account if p3881 has a value of 4 (technology controller) and the technology
controller is also active as the setpoint source.
p3884
CI: ESM setpoint technology controller / ESM setp tech_ctrl
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the technology controller's setpoint in emergency operation (ESM).
Note:
If p3884 = 0, the technology controller uses the setpoint from p2253.
r3887[0...1]
ESM number of activations and faults / ESM num activ+flt
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Indicates how often emergency operation (ESM) has been activated (index 0) and how many faults have occurred
during emergency operation (index 1).
Index:
[0] = Number of activations of emergency operation
[1] = Number of faults during emergency operation
p3888
ESM reset number of activations and faults / ESM reset act flts
Access level: 4
Can be changed: T
Units group: -
Min
0
Description:
Resets the number of activations of emergency operation and the number of faults which have occurred (in r3887).
0 = Do not reset
1 = Reset
1-330
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
1
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: U32 / Binary
Data set: -
Factory setting
0
Data type: U32 / FloatingPoint32
Data set: -
Factory setting
0
Data type: Unsigned16
Data set: -
Factory setting
-
Data type: Unsigned8
Data set: -
Factory setting
0
© Siemens AG 2011 All Rights Reserved