Parameters
List of Parameters
p1108[0...n]
BI: Total setpoint selection / Total setp sel
Access level: 4
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to select the total setpoint.
Dependency:
The selection of the total speed setpoint is automatically interconnected to the status word of the technology con-
troller (r2349.4) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
If the hibernation function is activated (p2398 = 1), an interconnection is made to r2399.7.
Refer to: p1109
Caution:
If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the inter-
connection to its status word (r2349.4). If the hibernation function is activated, then it is not permissible to disable
the interconnection to status word r2399.
p1109[0...n]
CI: Total setpoint / Total setp
Access level: 4
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the total setpoint.
For p1108 = 1 signal, the total setpoint is read in via p1109.
Dependency:
The signal source of the total setpoint is automatically interconnected to the output of the technology controller
(r2294) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
If the hibernation function is activated (p2398 = 1), an interconnection is made to r2397[0].
Refer to: p1108
Caution:
If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the inter-
connection to its output (r2294).
If the hibernation function is activated, then it is not permissible to withdraw the interconnection to setpoint r2398[0].
p1110[0...n]
BI: Inhibit negative direction / Inhib neg dir
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to disable the negative direction.
Dependency:
Refer to: p1111
p1111[0...n]
BI: Inhibit positive direction / Inhib pos dir
Access level: 4
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to disable the positive direction.
Dependency:
Refer to: p1110
1-142
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
1
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0