p1000[0...n]
Speed setpoint selection / n_set sel
CU230P-2 DP
Access level: 1
Can be changed: T
Units group: -
Min
0
Description:
Sets the source for the speed setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value:
0:
1:
2:
3:
6:
7:
10:
11:
12:
13:
16:
17:
20:
21:
22:
23:
26:
27:
30:
31:
32:
33:
36:
37:
60:
61:
62:
63:
66:
67:
70:
71:
72:
73:
76:
77:
200:
Dependency:
When changing this parameter, the following settings are influenced:
Refer to: p1070, p1071, p1075, p1076
Caution:
If p1000 is selected as the main setpoint of the fieldbus, the following BICO interconnection is set automatically:
p2051[1] = r0063
Caution:
When executing a specific macro, the corresponding programmed settings are made and become active.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
No main setpoint
Motorized potentiometer
Analog setpoint
Fixed speed setpoint
Fieldbus
Analog setpoint 2
Motor potentiometer + no main setpoint
Motor potentiometer + motor potentiometer
Motor potentiometer + analog setpoint
Motor potentiometer + fixed speed setpoint
Motor potentiometer + fieldbus
Motor potentiometer + analog setpoint 2
Analog setpoint + no main setpoint
Analog setpoint + motor potentiometer
Analog setpoint + analog setpoint
Analog setpoint + fixed speed setpoint
Analog setpoint + fieldbus
Analog setpoint + analog setpoint 2
Fixed speed setpoint + no main setpoint
Fixed speed setpoint + motor potentiometer
Fixed speed setpoint + analog setpoint
Fixed speed setpoint + fixed speed setpoint
Fixed speed setpoint + fieldbus
Fixed speed setpoint + analog setpoint 2
Fieldbus + no main setpoint
Fieldbus + motor potentiometer
Fieldbus + analog setpoint
Fieldbus + fixed speed setpoint
Fieldbus+fieldbus
Fieldbus + analog setpoint 2
Analog setpoint 2 + no main setpoint
Analog setpoint 2 + motor potentiometer
Analog setpoint 2 + analog setpoint
Analog setpoint 2 + fixed speed setpoint
Analog setpoint 2 + fieldbus
Analog setpoint 2 + analog setpoint 2
Analog output connection
Calculated: -
Scaling: -
Unit selection: -
Max
200
Parameters
List of Parameters
Data type: Integer16
Data set: CDS, p0170
Factory setting
6
1-123