p0356[0...n]
Motor stator leakage inductance / Mot L_stator leak.
Access level: 3
Can be changed: C(3), U, T
Units group: -
Min
0.00000 [mH]
Description:
Induction machine: sets the stator leakage inductance of the motor.
Synchronous motor: Sets the stator quadrature axis inductance of the motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910).
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
If the stator leakage inductance (p0356) for induction motors is changed outside the commissioning phase (p0010 >
0), the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). You are then advised to
repeat the measurement for the saturation characteristic (p1960).
For permanent-magnet synchronous motors (p0300 = 2), this is the non-saturated value and is, therefore, ideal for
a low current.
p0357[0...n]
Motor stator inductance, d axis / Mot L_stator d
Access level: 3
Can be changed: C(3), U, T
Units group: -
Min
0.00000 [mH]
Description:
Sets the stator direct-axis inductance of the synchronous motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910).
Note:
For permanent-magnet synchronous motors (p0300 = 2), this is the non-saturated value and is ideal for a low cur-
rent.
p0358[0...n]
Motor rotor leakage inductance / Mot L_rot leak
Access level: 3
Can be changed: C(3), U, T
Units group: -
Min
0.00000 [mH]
Description:
Sets the rotor/secondary section leakage inductance of the motor.
The value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification routine
(p1910).
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
If the rotor leakage inductance (p0358) for induction motors is changed outside the commissioning phase (p0010 >
0), then the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). You are then
advised to repeat the measurement for the saturation characteristic (p1960).
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: p0340 = 1,2
Scaling: -
Unit selection: -
Max
1000.00000 [mH]
Calculated: p0340 = 1,2
Scaling: -
Unit selection: -
Max
1000.00000 [mH]
Calculated: p0340 = 1,2
Scaling: -
Unit selection: -
Max
1000.00000 [mH]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: MDS
Factory setting
0.00000 [mH]
Data type: FloatingPoint32
Data set: MDS
Factory setting
0.00000 [mH]
Data type: FloatingPoint32
Data set: MDS
Factory setting
0.00000 [mH]
1-65