p11227
Free tec_ctrl 2 unit reference quantity / Ftec2 unit ref
Access level: 1
Can be changed: T
Units group: -
Min
0.01
Description:
Sets the reference quantity for the unit of the parameters of the free technology controller 2.
When changing over using changeover parameter p11226 to absolute units, all of the parameters involved refer to
the reference quantity.
Dependency:
Refer to: p11226
p11228
Free tec_ctrl 2 sampling time / Ftec2 t_samp
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the sampling time for the free technology controller 2.
Value:
0:
1:
2:
3:
4:
r11249.0...11
CO/BO: Free tec_ctrl 2 status word / Ftec2 stat_word
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the status word of the free technology controller 2.
Bit field:
Bit
Signal name
00
De-activated
01
Limited
08
Actual value at the minimum
09
Actual value at the maximum
10
Output at the minimum
11
Output at the maximum
p11253
CI: Free tec_ctrl 2 setpoint signal source / Ftec2 setp s_src
Access level: 2
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the setpoint of the free technology controller 2.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Reserved
128 ms
256 ms
512 ms
1024 ms
Calculated: -
Scaling: -
Unit selection: -
Max
340.28235E36
Calculated: -
Scaling: -
Unit selection: -
Max
4
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
1.00
Data type: Integer16
Data set: -
Factory setting
2
Data type: Unsigned32
Data set: -
Factory setting
-
0 signal
No
No
No
No
No
No
Data type: U32 / FloatingPoint32
Data set: -
Factory setting
0