r2245
CO: Technology controller mot. potentiometer setpoint before RFG /
Tec_ctr mop befRFG
Access level: 2
Can be changed: -
Units group: 9_1
Min
- [%]
Description:
Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator of the technology
controller.
Dependency:
Refer to: r2250
p2247[0...n]
Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
Access level: 2
Can be changed: U, T
Units group: -
Min
0.0 [s]
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2248
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
p2248[0...n]
Technology controller motorized potentiometer ramp-down time /
Tec_ctrMop t_rdown
Access level: 2
Can be changed: U, T
Units group: -
Min
0.0 [s]
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2247
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-down is correspondingly extended.
r2250
CO: Technology controller motorized potentiometer setpoint after RFG /
Tec_ctr mop aftRFG
Access level: 2
Can be changed: -
Units group: 9_1
Min
- [%]
Description:
Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency:
Refer to: r2245
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.0 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.0 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
10.0 [s]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
10.0 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
1-301