p2192[0...n]
Load monitoring delay time / Load monit t_del
Access level: 3
Can be changed: U, T
Units group: -
Min
0.00 [s]
Description:
Sets the delay time to evaluate the load monitoring.
p2193[0...n]
Load monitoring configuration / Load monit config
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Sets the load monitoring configuration.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
Refer to: A07920, A07921, A07922, F07923, F07924, F07925, F07936
p2194[0...n]
Torque threshold value 2 / M_thresh val 2
Access level: 3
Can be changed: U, T
Units group: -
Min
0.00 [%]
Description:
Sets the torque threshold value for the message "Torque utilization < torque threshold value 2" (BO: r2199.11).
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency:
Refer to: r0033, p2195, r2199
p2195[0...n]
Torque utilization switch-off delay / M_util t_off
Access level: 3
Can be changed: U, T
Units group: -
Min
0.0 [ms]
Description:
Sets the switch-off delay time for the negated signal "run-up completed".
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency:
Refer to: p2174, p2194
p2196[0...n]
Torque utilization scaling / M_util scal
Access level: 1
Can be changed: C(1, 3), U, T
Units group: -
Min
0.00 [%]
Description:
Sets the scaling factor for torque utilization (r0033).
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Monitoring switched out
Monitoring torque and load drop
Monitoring speed and load drop
Monitoring load drop
Calculated: -
Scaling: -
Unit selection: -
Max
65.00 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
100.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.0 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.00 [%]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
10.00 [s]
Data type: Integer16
Data set: DDS, p0180
Factory setting
1
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
90.00 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
800.0 [ms]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100.00 [%]
1-291