Parameters
List of Parameters
p1806[0...n]
Filter time constant Vdc correction / T_filt Vdc_corr
Access level: 4
Can be changed: U, T
Units group: -
Min
0.0 [ms]
Description:
Sets the filter time constant of the DC link voltage used to calculate the modulation depth.
r1808
DC link voltage actual value for U_max calculation / Vdc act val U_max
Access level: 4
Can be changed: -
Units group: 5_2
Min
- [V]
Description:
DC link voltage used to determine the maximum possible output voltage.
r1809
CO: Modulator mode actual / Modulator mode act
Access level: 4
Can be changed: -
Units group: -
Min
1
Description:
Displays the effective modulator mode.
Value:
1:
2:
p1810
Modulator configuration / Modulator config
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the configuration for the modulator.
Bit field:
Bit
Signal name
00
Avg value filter for U_lim (only for
Vdc_comp. in modulator)
01
DC link voltage compensation in the current
control
14
Deactivate maximum angular difference
adaptation
Notice:
Bit 1 = 1 can only be set under a pulse inhibit and for r0192.14 = 1.
Note:
Re bit 00 = 0:
Voltage limitation from the minimum of the DC link voltage (lower ripple in the output current, reduced output volt-
age).
Re bit 00 = 1:
Voltage limitation from averaged DC link voltage (higher output voltage with increased ripple in the output current).
The selection is only valid if the DC link compensation is not performed in the Control Unit (bit 1 = 0).
Re bit 01 = 0:
DC link voltage compensation in the modulator.
Re bit 01 = 1:
DC link voltage compensation in the current control.
1-230
Flat top modulation (FLB)
Space vector modulation (SVM)
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
10000.0 [ms]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
- [V]
Calculated: -
Scaling: -
Unit selection: -
Max
2
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.0 [ms]
Data type: FloatingPoint32
Data set: -
Factory setting
- [V]
Data type: Integer16
Data set: -
Factory setting
-
Data type: Unsigned16
Data set: -
Factory setting
0000 0000 0000 0000 bin
0 signal
No
No
No