p8608[0...1]
CAN Clear Bus Off Error / Clear bus off err
CU230P-2 CAN
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
As a result of a Bus Off error, the CAN controller is set into the initialization state.
Index 0:
The CAN controller is manually started after resolving the cause of the error with p8608[0] = 1
Index 1:
The automatic CAN bus start function is activated using p8608[1] = 1.
At 2 second intervals, the CAN controller is automatically restarted until the cause of the error has been resolved
and a CAN connection has been established.
Value:
0:
1:
Index:
[0] = Manual controller start function
[1] = Activating the automatic controller start function
Note:
Index 0:
This parameter is automatically reset to 0 after start.
p8609[0...1]
CAN Error Behavior / Error behavior
CU230P-2 CAN
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the behavior of the CAN node referred to the communications error or equipment fault.
Value:
0:
1:
2:
Index:
[0] = Behavior for communication errors
[1] = Behavior for device faults
Note:
Corresponds to the CANopen object 1029 hex.
r8610[0...1]
CAN First Server SDO / First server SDO
CU230P-2 CAN
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the identifier (client/server and server/client) of the SDO channel.
Index:
[0] = Displays the COB ID from client to server
[1] = Displays the COB ID from server to client
Note:
Corresponds to the CANopen object 1200 hex.
SDO: Service Data Object
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Inactive
Start CAN controller
Pre-operational
No change
Stopped
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
2
Calculated: -
Scaling: -
Unit selection: -
Max
-
Parameters
List of Parameters
Data type: Integer16
Data set: -
Factory setting
0
Data type: Integer16
Data set: -
Factory setting
1
Data type: Unsigned32
Data set: -
Factory setting
-
1-349