Parameters
List of Parameters
r8413.0...1
BO: RTC DTC1 output / RTC DTC1 output
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Display and binector output for the output of time switch 1 (DTC1).
Where a weekday is de-activated, the following applies (p8410):
- The binector output for this timer is inactive (r8413.0 = 0).
Where a weekday is activated, the following applies (p8410):
- The ON/OFF time setting (p8411, p8412) for this timer has an instant effect on the binector output (r8413).
Bit field:
Bit
Signal name
00
Timer on
01
Timer ON negated
Dependency:
Refer to: p8409, p8410, p8411, p8412
Notice:
This parameter can only be changed when p8409 = 0.
Note:
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8420[0...6]
RTC DTC2 weekday of activation / RTC DTC2 day act
Access level: 3
Can be changed: T
Units group: -
Min
0000 bin
Description:
Sets the weekday on which timer 2 is activated (DTC2).
The switch-on/off time is set in p8421/p8422 and the result displayed via binector output r8423.
Value:
0:
1:
Index:
[0] = Monday
[1] = Tuesday
[2] = Wednesday
[3] = Thursday
[4] = Friday
[5] = Saturday
[6] = Sunday
Dependency:
Refer to: p8409, p8421, p8422, r8423
Notice:
This parameter can only be changed when p8409 = 0.
Note:
DTC: Digital Time Clock (timer)
RTC: Real-time clock
1-342
Weekday de-activated
Weekday activated
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
No
Calculated: -
Scaling: -
Unit selection: -
Max
0001 bin
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: Unsigned16
Data set: -
Factory setting
-
0 signal
No
Yes
Data type: Integer16
Data set: -
Factory setting
0000 bin
© Siemens AG 2011 All Rights Reserved