Parameters
List of Parameters
p31022
Multi-zone control for actual value processing / Zone_ctrl act proc
Access level: 2
Can be changed: T
Units group: -
Min
0
Description:
Sets the processing method for the multi-zone control actual value (r31027).
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
11:
Note:
Re p31022 = 0, 1, 2:
Only actual value 1, 2, or 3 is used as r31027.
Re p31022 = 3:
The difference between actual values 1 and 2 is used as r31027.
Re p31022 = 4:
The sum of actual values 1 and 2 is used as r31027.
Re p31022 = 5:
The sum of actual values 1, 2, and 3 is used as r31027.
Re p31022 = 6:
The mean value of actual values 1 and 2 is used as r31027.
Re p31022 = 7:
The mean value of actual values 1, 2 and 3 is used as r31027.
Re p31022 = 8:
The lower value of actual values 1 and 2 is used as r31027.
Re p31022 = 9:
The lowest value of actual values 1, 2, and 3 is used as r31027.
Re p31022 = 10:
The higher value of actual values 1 and 2 is used as r31027.
Re p31022 = 11:
The highest value of actual values 1, 2, and 3 is used as r31027.
p31023[0...3]
CI: Multi-zone control setpoint input / Zone_ctrl setp inp
Access level: 2
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the multi-zone control setpoints.
1-468
Only act 1
Only act 2
Only act 3
Difference (actual value 1, 2)
Sum (actual value 1, 2)
Sum (actual value 1, 2 and 3)
Mean value (actual value 1, 2)
Mean value (actual value 1, 2 and 3)
Minimum (actual value 1, 2)
Minimum (actual value 1, 2 and 3)
Maximum (actual value 1, 2)
Maximum (actual value 1, 2 and 3)
Calculated: -
Scaling: -
Unit selection: -
Max
11
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: Integer16
Data set: -
Factory setting
0
Data type: U32 / FloatingPoint32
Data set: -
Factory setting
0