Siemens SINAMICS G120 Manual page 157

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

p1203[0...n]
Flying restart search rate factor / FlyRst v_Srch Fact
PM240
Access level: 3
PM250, PM260
Can be changed: U, T
Units group: -
Min
10 [%]
Description:
The value influences the rate at which the output frequency is changed during a flying restart . A higher value
results in a longer search time.
Caution:
An unfavorable parameter value can result in the motor behaving in an uncontrollable fashion.
For vector control, a value that is too low or too high can cause flying restart to become unstable.
Note:
The parameter factory setting is selected so that standard induction motors that are rotating can be found and
restarted as quickly as possible (fast flying restart).
With this pre-setting, if the motor is not found (e.g. for motors that are accelerated as a result of active loads or with
U/f control and low speeds), we recommend that the search rate is reduced (by increasing p1203).
r1204.0...13
CO/BO: Flying restart, U/f control status / FlyRest Uf st
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays the status for checking and monitoring flying restart states in the U/f control mode.
Bit field:
Bit
Signal name
00
Current impressed
01
No current flow
02
Voltage input
03
Voltage reduced
04
Start ramp-function generator
05
Wait for execution
06
Slope filter act
07
Positive gradient
08
Current < thresh
09
Current minimum
10
Search in the positive direction
11
Stop after positive direction
12
Stop after negative direction
13
No result
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
4000 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100 [%]
Data type: Unsigned16
Data set: -
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
No
No
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1-157

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2

Table of Contents