r0070
CO: Actual DC link voltage / Vdc act val
Access level: 3
Can be changed: -
Units group: 5_2
Min
- [V]
Description:
Displays the measured actual value of the DC link voltage.
Dependency:
Refer to: r0026
Notice:
When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM240) a valid measured value is not sup-
plied. In this case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the dis-
play parameter.
Note:
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0071
Maximum output voltage / U_output max
Access level: 3
Can be changed: -
Units group: 5_1
Min
- [Vrms]
Description:
Displays the maximum output voltage.
Dependency:
The maximum output voltage depends on the actual DC link voltage (r0070) and the maximum modulation depth
(p1803).
Note:
As the (driven) motor load increases, the maximum output voltage drops as a result of the reduction in DC link volt-
age.
r0072
CO: Output voltage / U_output
Access level: 3
Can be changed: -
Units group: 5_1
Min
- [Vrms]
Description:
Displays the actual output voltage of the power unit.
Dependency:
Refer to: r0025
Note:
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
r0073
Maximum modulation depth / Modulat_depth max
Access level: 4
Can be changed: -
Units group: -
Min
- [%]
Description:
Displays the maximum modulation depth.
Dependency:
Refer to: p1803
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
- [V]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
- [Vrms]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
- [Vrms]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
- [V]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Vrms]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Vrms]
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
1-37