Parameters
List of Parameters
p1786[0...n]
Motor model Lh adaptation integral time / MotMod Lh Tn
Access level: 4
Can be changed: U, T
Units group: -
Min
10 [ms]
Description:
Sets the integral time for the Lh adaptation of the motor model for an induction motor (ASM).
r1787[0...n]
Motor model Lh adaptation corrective value / MotMod Lh corr
Access level: 4
Can be changed: -
Units group: -
Min
- [mH]
Description:
Displays the corrective value for the Lh adaptation of the motor model for an induction motor (ASM).
Dependency:
Refer to: p0826, p1780
Note:
The adaptation result is reset if the magnetizing inductance of the induction motor is changed (p0360, r0382). This
also happens when changing over the data set if a different motor is not being used (p0826).
The display of the inactive data sets is only updated when changing over the data set.
r1791
Motor model Lh adaptation power-on frequency / MotMod Lh f_on
Access level: 4
Can be changed: -
Units group: -
Min
- [Hz]
Description:
Displays the power-on stator frequency/ primary section frequency for the Lh adaptation for the induction motor
(ASM).
r1792
Motor model Lh adaptation power-on slip / MotMod Lh fslip
Access level: 4
Can be changed: -
Units group: -
Min
- [Hz]
Description:
Displays the power-on slip frequency for the Lh adaptation for the induction motor (ASM).
p1795[0...n]
Motor model kT adaptation integral time / MotMod kT Tn
Access level: 4
Can be changed: U, T
Units group: -
Min
10 [ms]
Description:
Sets the integral time of the kT adaptation of the motor model for a permanent-magnet synchronous motor (PEM).
1-226
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
- [mH]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Hz]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Hz]
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
10000 [ms]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100 [ms]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
- [mH]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Hz]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Hz]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100 [ms]