p1802[0...n]
Modulator mode / Modulator mode
PM250
Access level: 3
PM260
Can be changed: T
Units group: -
Min
0
Description:
Sets the modulator mode.
Value:
0:
2:
3:
4:
Dependency:
If a sine-wave filter is parameterized as output filter (p0230 = 3, 4), then only space vector modulation without over-
control can be selected as modulation type (p1802 = 3). This is not valid for the power units PM260. p1802 = 10 can
only be set for the PM230 and PM240 power units.
Refer to: p0230, p0500
Note:
When modulation modes are enabled that could lead to overmodulation (p1802 = 0, 2,10), the modulation depth
must be limited using p1803 (default p1803 < 100 %). The higher the overmodulation, the greater the current ripple
and torque ripple.
When changing p1802[x], the values for all of the other existing indices are also changed.
p1803[0...n]
Maximum modulation depth / Modulat depth max
PM230
Access level: 4
Can be changed: U, T
Units group: -
Min
20.0 [%]
Description:
Defines the maximum modulation depth.
Dependency:
Refer to: p0500
Note:
p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
p1803[0...n]
Maximum modulation depth / Modulat depth max
PM240
Access level: 3
Can be changed: U, T
Units group: -
Min
20.0 [%]
Description:
Defines the maximum modulation depth.
Dependency:
Refer to: p0500
Note:
p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
p1803[0...n]
Maximum modulation depth / Modulat depth max
PM250
Access level: 3
PM260
Can be changed: U, T
Units group: -
Min
20.0 [%]
Description:
Defines the maximum modulation depth.
Dependency:
Default setting PM260: 103 %.
Refer to: p0500
Note:
p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Automatic changeover SVM/FLB
Space vector modulation (SVM)
SVM without overcontrol
SVM/FLB without overcontrol
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
4
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
120.0 [%]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
150.0 [%]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
150.0 [%]
Parameters
List of Parameters
Data type: Integer16
Data set: DDS, p0180
Factory setting
4
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
115.0 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
106.0 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
106.0 [%]
1-229