Parameters
List of Parameters
p1326[0...n]
U/f control programmable characteristic frequency 4 / Uf char f4
Access level: 3
Can be changed: U, T
Units group: -
Min
0.00 [Hz]
Description:
The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the frequency of the fourth point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
The following applies for the frequency values:
p1320 <= p1322 <= p1324 <= p1326
Otherwise, a standard characteristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1325, p1327
Note:
Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327. For output fre-
quencies above p1326, the characteristic is extrapolated with the gradient between the characteristic points
p1324/p1325 and p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
p1327[0...n]
U/f control programmable characteristic voltage 4 / Uf char U4
Access level: 3
Can be changed: U, T
Units group: -
Min
0.0 [Vrms]
Description:
The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the fourth point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1325, p1326
Note:
Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
p1330[0...n]
CI: U/f control independent voltage setpoint / Uf U_set independ.
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the voltage setpoint for U/f control with an independent voltage setpoint (p1300 = 19).
Dependency:
Selects the U/f control with independent voltage setpoint via p1300 = 19.
Refer to: p1300
1-184
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
10000.00 [Hz]
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
10000.0 [Vrms]
Calculated: -
Scaling: p2001
Unit selection: -
Max
-
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [Hz]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.0 [Vrms]
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
© Siemens AG 2011 All Rights Reserved