Parameters
List of Parameters
p1145[0...n]
Ramp-function generator tracking intensity. / RFG track intens
Access level: 4
Can be changed: U, T
Units group: -
Min
0.0
Description:
Sets the ramp-function generator tracking.
The output value of the ramp-function generator is tracked (corrected) corresponding to the maximum possible
drive acceleration. The reference value is the deviation at the speed/velocity controller input that is necessary to
ensure that the motor accelerates at the torque/force limit.
Notice:
If ramp-function generator tracking is activated and the ramp time is set too short, this can cause unsteady acceler-
ation.
Remedy:
- switch off ramp-function generator tracking (p1145 = 0).
- increase the ramp-up/ramp-down time (p1120, p1121).
Note:
In the U/f mode, ramp-function generator tracking is not active.
p1148[0...n]
Ramp-function gen., tolerance for ramp-up and ramp-down active / RFG tol HL/RL act
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.000 [rpm]
Description:
Sets the tolerance value for the status of the ramp-function generator (ramp-up active, ramp-down active).
If the input of the ramp-function generator does not change in comparison to the output by more than the entered
tolerance time, then the status bits "ramp-up active" and "ramp-down active" are not influenced.
Dependency:
Refer to: r1199
r1149
CO: Ramp-function generator, acceleration / RFG acceleration
Access level: 3
Can be changed: -
Units group: 39_1
Min
- [rev/s²]
Description:
Displays the acceleration of the ramp-function generator.
Dependency:
Refer to: p1145
r1150
CO: Ramp-function generator speed setpoint at the output / RFG n_set at outp
Access level: 4
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Displays the setpoint at the output of the ramp-function generator.
1-152
Calculated: -
Scaling: -
Unit selection: -
Max
50.0
Calculated: -
Scaling: -
Unit selection: p0505
Max
1000.000 [rpm]
Calculated: -
Scaling: p2007
Unit selection: p0505
Max
- [rev/s²]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.0
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
19.800 [rpm]
Data type: FloatingPoint32
Data set: -
Factory setting
- [rev/s²]
Data type: FloatingPoint32
Data set: -
Factory setting
- [rpm]
© Siemens AG 2011 All Rights Reserved