F07925
Drive: Torque/speed out of tolerance
Reaction:
OFF1 (NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
For p2193 = 1:
The torque deviates from the torque/speed envelope characteristic.
For p2193 = 2:
The speed signal from the external encoder (refer to p3230) deviates from the speed (r2169).
Remedy:
- check the connection between the motor and load.
- adapt the parameterization corresponding to the load.
A07927
DC braking active
Reaction:
NONE
Acknowledge:
NONE
Cause:
The motor is braked with DC current. DC braking is active.
1)
A message with response DCBRK is active. The motor is braked with the braking current set in p1232 for the duration
set in in p1233. If the standstill threshold p1226 is undershot, then braking is prematurely canceled.
2)
DC braking has been activated at binector input p1230 with the DC braking set (p1230 = 4). Braking current p1232
is injected until this binector input becomes inactive.
Remedy:
Not necessary.
The alarm automatically disappears once DC braking has been executed.
A07929 (F)
Drive: No motor detected
Reaction:
NONE
Acknowledge:
NONE
Cause:
The absolute current value is so small after enabling the inverter pulses that no motor is detected.
Note:
In the case of vector control and an induction motor, this alarm is followed by the fault F07902.
See also: p2179 (Output load identification current limit)
Remedy:
- check the motor feeder cables.
- reduce the threshold value (p2179), e.g. for synchronous motors.
- check the voltage boost of the U/f control (p1310).
- carry out a standstill measurement to set the stator resistance (p0350).
F07936
Drive: load failure
Reaction:
OFF1 (NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The load monitoring has detected a load failure.
Remedy:
- check the sensor.
- if necessary, de-activate the load monitoring (p2193).
See also: p2193 (Load monitoring configuration), p3232 (Load monitoring failure detection)
F07950 (A)
Motor parameter incorrect
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The motor parameters were incorrectly entered while commissioning (e.g. p0300 = 0, no motor)
Fault value (r0949, decimal interpretation):
Parameter number involved.
See also: p0300, p0301, p0304, p0305, p0307, p0310, p0311, p0314, p0316, p0320, p0322, p0323
Remedy:
Compare the motor data with the rating plate data and if required, correct.
See also: p0300, p0301, p0304, p0305, p0307, p0310, p0311, p0314, p0316, p0320, p0322, p0323
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Faults and Alarms
List of Faults and Alarms
3-691