Parameters
List of Parameters
p11174
Free tec_ctrl 1 differentiation time constant / Ftec1 D comp T
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the time constant for the differentiation (D component) of the free technology controller 1.
Note:
Value = 0: Differentiation is de-activated.
p11180
Free tec_ctrl 1 proportional gain / Ftec1 Kp
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000
Description:
Sets the proportional gain (P component) of the free technology controller 1.
Note:
Value = 0: The proportional gain is de-activated.
p11185
Free tec_ctrl 1 integral time / Ftec1 Tn
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the integral time (I component, integrating time constant) of the free technology controller 1.
Note:
Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
p11191
CO: Free tec_ctrl 1 limit maximum / Ftec1 lim max
Access level: 3
Can be changed: U, T
Units group: -
Min
-200.00 [%]
Description:
Sets the maximum limit of the free technology controller 1.
Dependency:
Refer to: p11192
Note:
The maximum limit must always be greater than the minimum limit (p11191 > p11192).
p11192
CO: Free tec_ctrl 1 limit minimum / Ftec1 lim min
Access level: 3
Can be changed: U, T
Units group: -
Min
-200.00 [%]
Description:
Sets the minimum limit of the free technology controller 1.
Dependency:
Refer to: p11191
Note:
The maximum limit must always be greater than the minimum limit (p11191 > p11192).
1-388
Calculated: -
Scaling: -
Unit selection: -
Max
60.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.000
Calculated: -
Scaling: -
Unit selection: -
Max
10000.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
0.000 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
1.000
Data type: FloatingPoint32
Data set: -
Factory setting
30.000 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [%]
Data type: FloatingPoint32
Data set: -
Factory setting
0.00 [%]
© Siemens AG 2011 All Rights Reserved