Siemens SINAMICS G120 Manual page 147

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

p1134[0...n]
Ramp-function generator rounding-off type / RFG round-off type
Access level: 2
Can be changed: U, T
Units group: -
Min
0
Description:
Sets the smoothed response to the OFF1 command or the reduced setpoint for the extended ramp-function gener-
ator.
Value:
0:
1:
Dependency:
No effect up to initial rounding-off time (p1130) > 0 s.
Note:
p1134 = 0 (continuous smoothing)
If the setpoint is reduced while ramping-up, initially a final rounding-off is carried out and then the ramp-up com-
pleted. During the final rounding-off, the output of the ramp-function generator continues to go in the direction of the
previous setpoint (overshoot). After the final rounding-off has been completed, the output goes toward the new set-
point.
p1134 = 1 (discontinuous smoothing)
If the setpoint is reduced while ramping-up, then the output goes immediately in the direction of the new setpoint.
For the setpoint change there is no rounding-off.
p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
PM230
Access level: 2
Can be changed: C(1), U, T
Units group: -
Min
0.000 [s]
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Dependency:
The parameter is pre-assigned depending on the size of the power unit.
Note:
This time can be exceeded if the DC link voltage reaches its maximum value.
p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
PM240
Access level: 2
PM250, PM260
Can be changed: C(1), U, T
Units group: -
Min
0.000 [s]
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note:
This time can be exceeded if the DC link voltage reaches its maximum value.
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
PM230
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Cont. smoothing
Discont smoothing
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
5400.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
5400.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
30.000 [s]
Parameters
List of Parameters
Data type: Integer16
Data set: DDS, p0180
Factory setting
0
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
30.000 [s]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.000 [s]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
2.000 [s]
1-147