Faults and Alarms
List of Faults and Alarms
F01039 (A)
ACX: Writing to the parameter back-up file was unsuccessful
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
Writing to at least one parameter back-up file PSxxxyyy.*** in the non-volatile memory was unsuccessful.
- In the directory /USER/SINAMICS/DATA/ at least one parameter back-up file PSxxxyyy.*** has the "read only" file
attribute and cannot be overwritten.
- There is not sufficient free memory space available.
- The non-volatile memory is defective and cannot be written to.
Fault value (r0949, interpret hexadecimal):
dcba hex
a = yyy in the file names PSxxxyyy.***
a = 000 --> consistency back-up file
a = 001 ... 062 --> drive object number
a = 099 --> PROFIBUS parameter back-up file
b = xxx in the file names PSxxxyyy.***
b = 000 --> data save started with p0971 = 1
b = 010 --> data save started with p0971 = 10
b = 011 --> data save started with p0971 = 11
b = 012 --> data save started with p0971 = 12
d, c:
Only for internal Siemens troubleshooting.
Remedy:
- check the file attribute of the files (PSxxxyyy.***, CAxxxyyy.***, CCxxxyyy.***) and, if required, change from "read
only" to "writeable".
- check the free memory space in the non-volatile memory. Approx. 80 kbyte of free memory space is required for
every drive object in the system.
- replace the memory card or Control Unit.
F01040
Save parameter settings and carry out a POWER ON
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
A parameter has been changed that requires the parameters to be backed up and the Control Unit to be switched
OFF and ON again.
Remedy:
- Save parameters (p0971).
- Switch Control Unit OFF/ON (POWER ON).
3-664
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
© Siemens AG 2011 All Rights Reserved