Parameters
List of Parameters
p2398
Hibernation operating mode / Hib op_mode
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the operating mode for the "Hibernation" function.
Value:
0:
1:
Dependency:
Refer to: p2200, p2251
Refer to: A07325
Caution:
When this function is active, the motor can start again automatically.
Note:
When the "hibernation" function (p2398 = 1) is activated, its behavior is defined as to whether the technology con-
troller is additionally switched in (closed-loop) or switched out (open-loop).
The technology controller is enabled via binector input p2200 and its mode is set in p2251.
p2200 = 0, p2251 = 0, 1:
Hibernation operates without technology controller (open-loop)
p2200 = 1, p2251 = 0:
Hibernation operates with technology controller (closed-loop)
p2200 = 1, p2251 = 1:
Hibernation operates without technology controller (open-loop) as its output is only used as supplementary setpoint
and not as main setpoint.
r2399.0...8
CO/BO: Hibernation status word / Hib ZSW
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the status word for the "Hibernation" function.
Bit field:
Bit
Signal name
00
Hibernation enabled (p2398 <> 0)
01
Hibernation active
02
Hibernation delay time active
03
Hibernation boost active
04
Hibernation motor powered down
05
Hibernation motor powered down cyclic
restart active
06
Hibernation motor restarts
07
Hibernation supplies total setpoint for ramp-
function generator
08
Hibernation bypasses ramp-fct generator in
setpoint channel
Dependency:
Refer to: p2398
Refer to: A07325
1-320
Hibernation inhibited
Hibernation active
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: Integer16
Data set: -
Factory setting
0
Data type: Unsigned32
Data set: -
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
© Siemens AG 2011 All Rights Reserved