Parameters
List of Parameters
p0724
CU digital inputs debounce time / CU DI t_debounce
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000 [ms]
Description:
Sets the debounce time for digital inputs.
Note:
The digital inputs are read in cyclically every 2 ms (DI 11, DI 12 every 4 ms).
To debounce the signals, the set debounce time is converted into integer multiple debounce clock cycles Tp (Tp =
p0724 / 2 ms).
DI: Digital Input
p0730
BI: CU signal source for terminal DO 0 / CU S_src DO 0
Access level: 2
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for terminal DO 0 (NO: T. 19 / NC: T. 18)
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
p0731
BI: CU signal source for terminal DO 1 / CU S_src DO 1
Access level: 2
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for terminal DO 1 (NO: T. 21).
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
p0732
BI: CU signal source for terminal DO 2 / CU S_src DO 2
Access level: 2
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for terminal DO 2 (NO: T. 24 / NC: T. 23).
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
1-88
Calculated: -
Scaling: -
Unit selection: -
Max
20.000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
4.000 [ms]
Data type: U32 / Binary
Data set: -
Factory setting
52.3
Data type: U32 / Binary
Data set: -
Factory setting
52.7
Data type: U32 / Binary
Data set: -
Factory setting
52.2
© Siemens AG 2011 All Rights Reserved