Siemens SINAMICS G120 Manual page 381

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

p11067
Free tec_ctrl 0 actual value upper limit / Ftec0 act v up lim
Access level: 3
Can be changed: U, T
Units group: 9_2
Min
-200.00 [%]
Description:
Sets the upper limit for the actual value signal of the free technology controller 0.
Dependency:
Refer to: p11064
p11068
Free tec_ctrl 0 actual value lower limit / Ftec0 act v lo lim
Access level: 3
Can be changed: U, T
Units group: 9_2
Min
-200.00 [%]
Description:
Sets the lower limit for the actual value signal of the free technology controller 0.
Dependency:
Refer to: p11064
p11071
Free tec_ctrl 0 actual value inversion / Ftec0 act v inv
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the inversion of the actual value signal of the free technology controller 0.
Value:
0:
1:
r11072
CO: Free tec_ctrl 0 actual value after limiter / Ftec0 act v af lim
Access level: 2
Can be changed: -
Units group: 9_2
Min
- [%]
Description:
Display and connector output for the actual value after the limiter of the free technology controller 0.
r11073
CO: Free tec_ctrl 0 system deviation / Ftec0 sys dev
Access level: 2
Can be changed: -
Units group: 9_2
Min
- [%]
Description:
Display and connector output for the system deviation of the free technology controller 0.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
No inversion
Inversion
Calculated: -
Scaling: PERCENT
Unit selection: p11026
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p11026
Max
200.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: PERCENT
Unit selection: p11026
Max
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: p11026
Max
- [%]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [%]
Data type: FloatingPoint32
Data set: -
Factory setting
-100.00 [%]
Data type: Integer16
Data set: -
Factory setting
0
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
1-381

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2

Table of Contents