Siemens SINAMICS G120 Manual page 23

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

r0028
Modulation depth smoothed / Mod_depth smth
Access level: 4
Can be changed: -
Units group: -
Min
- [%]
Description:
Displays the smoothed actual value of the modulation depth.
Dependency:
Refer to: r0074
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
r0029
Current actual value field-generating smoothed / Id_act smooth
Access level: 4
Can be changed: -
Units group: -
Min
- [Arms]
Description:
Displays the smoothed field-generating actual current.
Dependency:
Refer to: r0076
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
r0030
Current actual value torque-generating smoothed / Iq_act smooth
Access level: 4
Can be changed: -
Units group: -
Min
- [Arms]
Description:
Displays the smoothed torque-generating actual current.
Dependency:
Refer to: r0078
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque-generating current actual value is available smoothed (r0030) and unsmoothed (r0078).
r0031
Actual torque smoothed / M_act smooth
Access level: 2
Can be changed: -
Units group: 7_1
Min
- [Nm]
Description:
Displays the smoothed torque actual value.
Dependency:
Refer to: r0080
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The active current actual value is available smoothed (r0031) and unsmoothed (r0080).
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: p2002
Unit selection: -
Max
- [%]
Calculated: -
Scaling: p2002
Unit selection: -
Max
- [Arms]
Calculated: -
Scaling: p2002
Unit selection: -
Max
- [Arms]
Calculated: -
Scaling: p2003
Unit selection: p0505
Max
- [Nm]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Arms]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Arms]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Nm]
1-23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2

Table of Contents