r1751
Motor model status / MotMod status
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the status of the motor model.
Bit field:
Bit
Signal name
00
Controlled operation
01
Set ramp-function generator
02
Stop RsLh adaptation
03
Feedback
05
Holding angle
06
Acceleration criterion
07
Set angular integrator PEM
08
Stop Kt adaptation PEM
09
PolID active PEM SLVC
10
I injection PEM
11
Speed controller output cannot be set to
zero
12
Rs adapt waits
13
Motor operation
14
Stator frequency sign
15
Torque sign
16
Pulse injection active PEM
17
Operation with feedback
p1755[0...n]
Motor model changeover speed encoderless operation / MotMod n_chgSnsorl
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed to change over the motor model to encoderless operation.
Dependency:
Refer to: p1756
Notice:
The changeover speed represents the steady-state minimum speed up to which the motor model can be used
in steady-state operation without encoder.
If the stability is not adequate close to the changeover speed, it may make sense to increase the parameter value.
Note:
The changeover speed applies for the changeover between open-loop and closed-loop control mode.
p1756
Motor model changeover speed hysteresis encoderless operation /
MotMod n_chgov hys
Access level: 3
Can be changed: U, T
Units group: -
Min
0.0 [%]
Description:
Sets the hysteresis for the changeover speed of the motor model for encoderless operation.
Dependency:
Refer to: p1755
Note:
The parameter value refers to p1755.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Active
Active
Yes
Active
Yes
Active
No
No
No
No
Yes
Yes
Yes
Positive
Motor mode
Yes
Selected
Calculated: p0340 = 1,3
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
95.0 [%]
Parameters
List of Parameters
Data type: Unsigned32
Data set: -
Factory setting
-
0 signal
Inactive
Inactive
No
Inactive
No
Inactive
Yes
Yes
Yes
Yes
No
No
No
Negative
Regenerative mode
No
Deselected
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
210000.00 [rpm]
Data type: FloatingPoint32
Data set: -
Factory setting
50.0 [%]
FP
6721
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1-221