Siemens SINAMICS G120 Manual page 49

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

p0278
DC link voltage undervoltage threshold reduction / Vdc U_under red
Access level: 3
Can be changed: T
Units group: -
Min
-80 [V]
Description:
Sets the absolute value by which the threshold to initiate the undervoltage fault (F30003) is reduced.
Dependency:
Refer to: p0210, r0296
Refer to: F30003
Notice:
When using a Control Supply Module (CSM) for 24 V supply from the DC link, the minimum continuous DC link volt-
age may not lie below 430 V. DC link voltages in the range 300 ... 430 V are permissible up to a duration of 1 min.
For chassis power units, this parameter has no significance.
Note:
The resulting shutdown threshold can be read in r0296 and is dependent on the selected rated voltage (p0210) and
the power unit being used.
p0287[0...1]
Ground fault monitoring thresholds / Gnd flt threshold
Access level: 3
Can be changed: T
Units group: -
Min
0.0 [%]
Description:
Sets the shutdown thresholds for the ground fault monitoring.
The setting is made as a percentage of the maximum power unit current (r0209).
Index:
[0] = Threshold at which pre-charging starts
[1] = Threshold at which pre-charging stops
Dependency:
Refer to: F30021
r0289
CO: Maximum power unit output current / PU I_outp max
Access level: 3
Can be changed: -
Units group: -
Min
- [Arms]
Description:
Displays the actual maximum output current of the power unit taking into account derating factors.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
0 [V]
Calculated: -
Scaling: -
Unit selection: -
Max
100.0 [%]
Calculated: -
Scaling: p2002
Unit selection: -
Max
- [Arms]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
0 [V]
Data type: FloatingPoint32
Data set: -
Factory setting
[0] 6.0 [%]
[1] 16.0 [%]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Arms]
1-49

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2

Table of Contents