2.2 PoE PSU Supervision Configuration Commands

2.2.1 poe-power input-thresh lower
Syntax
poe-power input-thresh lower string
View
System view
Parameter
string: Undervoltage alarm threshold. It ranges from 90.00 V to 264.00 V in the format
of X.X and within the accuracy of the second decimal.
Description
Use the poe-power input-thresh lower command to set the undervoltage alarm
threshold of AC input for the PoE PSUs (lower threshold):
For 220 VAC input, it is recommended to set the threshold to 181.0 V.
For 110 VAC input, it is recommended to set the threshold to 90.0 V.
Example
# Set the undervoltage alarm threshold of AC input to 181.0 V.
[Quidway] poe-power input-thresh lower 181.0
Set lower input-threshold power successfully!
2.2.2 poe-power input-thresh upper
Syntax
poe-power input-thresh upper string
View
System view
Parameter
string: Overvoltage alarm threshold. It ranges from 90 V to 264 V in the format of X.X.
Description
Use the poe-power input-thresh upper command to set overvoltage alarm threshold
of AC input (upper threshold):
For 220 VAC input, it is recommended to set the threshold to 264.0 V.
For 110 VAC input, it is recommended to set the threshold to 132.0 V.
Huawei Technologies Proprietary
2-6
Chapter 2 PoE PSU Supervision Commands