8.7 Commissioning
8.7.3

Commissioning the safety terminals by means of STARTER/SCOUT

8.7.3.1

Basic sequence of commissioning

The following conditions must be met before you can configure the safety terminals:
● Concluded initial commissioning of the drive
● Measuring function (static or rotating measurement) completed
Table 8- 20
1
2
3
4
5
6
8
9
10
11
12
13
436
Configuration sequence
Step
Configuring safety terminals
Configure the inputs
Configure the output
Configuring Safety functions
Set the Safety password
Copy redundant parameters using "Copy parameters"
Activate the configuration by selecting "Activate settings"
Save the project in the drive by selecting "Copy RAM to ROM"
Load the project into the STARTER
Save the project in STARTER
Execute POWER ON
Carry out an acceptance test
Execution
Function Manual, 01/2011, 6SL3097-4AB10-0BP3