Safety Integrated Functions
8.9 Acceptance test and acceptance report
No.
3.
Deselect STO and check the following:
No Safety faults and alarms (r0945[0..7], r2122[0..7])
r9772.17 = r9872.17 = 0 (STO deselection via terminals - DI CU / EP terminal Motor
Module); only relevant for STO via terminal
r9772.20 = r9872.20 = 0 (STO deselection via PROFIsafe); only relevant for STO via
PROFIsafe
r9772.0 = r9772.1 = 0 (STO deselected and inactive – P1)
r9872.0 = r9872.1 = 0 (STO deselected and inactive – P2)
r9773.0 = r9773.1 = 0 (STO deselected and inactive – P1 + P2)
r0046.0 = 1 (drive in "Switching On Inhibited" status)
4.
Acknowledge "Switching On Inhibited" and run the drive. Ensure that the correct drive is running.
The following is tested:
Correct DRIVE-CLiQ wiring between Control Unit and Motor Modules
Correct assignment of drive No. – Motor Module – motor
The hardware is functioning properly
Correct wiring of the switch-off signal path (only via terminal)
Correct assignment of the terminals for STO on the Control Unit
Correct parameterization of the STO function
Forced checking procedure of the shutdown paths
476
Description
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Status
Function Manual

Hide quick links: