Commissioning with PROFIBUS
3.2 STARTER commissioning tool
Load to PG/PC
You can use this function to load the current Control Unit project to STARTER.
This function can be activated as follows:
● Right-click Drive unit → Target device → Load to PG/PC
● Drive unit grayed out → Load project to PG/PC button
● Online/offline comparison screen → Load project to PG/PC button
Restoring the factory settings
You can use this function (p0970 = 1) to set all the parameters in the work memory of the
Control Unit to the factory settings. The CU305 will then perform an automatic start. All
relevant parameters found are written to the work memory (RAM). As part of this process,
various factory-set parameters are automatically updated to actual (more recent) values.
Once this automatic configuration is complete, a project with all available drive parameters
for the actual arrangement will be available in the target system.
This function, which is called "Restore factory settings", can be activated as follows:
● Right-click Drive unit → Target device → Restore factory settings
● Drive unit grayed out → Restore factory settings button
Displaying toolbars
The toolbars can be activated by choosing View → Toolbars (check mark).
Creating and copying data sets (offline)
Drive and command data sets (DDS and CDS) can be added in the drive's configuration
screen. The corresponding buttons must be clicked.
For more information about data sets, see the Drive system principles chapter.
Upgrading firmware and the project in STARTER
Preconditions are a functional project, a memory card containing the new firmware and a
current version of STARTER.
Upgrade the project
1. Is the project in STARTER? Yes: continue with 3.
48
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Function Manual