● Control type: Speed control or Position control
● Encoder channel
● Encoder evaluation
● The pulse number is calculated from the maximum clock frequency of the controller and
● Select one of the following two options for the Signal shape:
Table 7- 21
Signal shapes for the pulse/direction interface
Signal shape
p0405[E].5
Pulse/direction
1
positive logic
A and B track
0
positive logic
● The CU305 automatically links the control signals to the specified inputs/outputs (see the
Setpoint value specification via pulse encoder emulation
● For relevant wiring information, refer to the table for "Setpoint value specification:
● As well making the settings in the commissioning wizard (see above), you also need to
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
The pulse/direction interface is assigned an encoder channel. If you are using a motor
encoder, it is always assigned encoder channel 1. This means you need to select
encoder channel 2 for the pulse/direction interface.
Select the integrated HTL/TTL encoder evaluation of the CU305 as the input for the
pulse/direction interface.
the preferred maximum motor speed. The following formula applies:
Pulse number = (max. clock frequency · 60)/max. speed
Example: If the controller has a maximum clock frequency of 100 kHz and the motor
being used is to run at its maximum rated speed of 3000 rpm, the resulting pulse number
will be 2000.
Graphic
"Wiring control signals" section).
Encoder signal with TTL level".
set the following values in the drive's expert list:
– p0405.0 = 1 (bipolar)
– p0405.1 = 1 (TTL)
Drive functions
7.1 Servo control