Safety Integrated Functions
8.9 Acceptance test and acceptance report
No.
4.
Analyze trace:
If r9714[0] exceeds the active SLS limit, a Safety message (r9722.7 = 0) becomes
active
A STOP B is initiated as a consequence (with subsequent stop STOP A)
5.
Save/print the trace and add it to the acceptance report (refer to the example below)
6.
Deselect SLS and acknowledge Safety messages
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7])
r0046.0 = 1 (drive in "Switching On Inhibited" status)
Acknowledge "Switching On Inhibited" and run the drive
Check the drive is moving.
Example trace SLS with STOP B
Figure 8-43
Example trace: SLS with STOP B
496
Description
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Status
Function Manual