Digital Inputs/Outputs - Siemens Sinamics S110 Function Manual

Hide thumbs Also See for Sinamics S110:
Table of Contents

Advertisement

10.5.2

Digital inputs/outputs

Digital inputs
Properties
● The digital inputs are "high active".
● An open input is interpreted as "low".
● Fixed debouncing setting
● Availability of the input signal for further interconnection
● Simulation mode settable and parameterizable.
● Isolation block by block, set by jumper.
Function diagrams (see SINAMICS S110 List Manual)
● 2020 Digital inputs, electrically isolated (DI 0 ... DI 3)
● 2021 Digital inputs, electrically isolated (DI 16 ... DI 19)
● 2022 Digital inputs, electrically isolated (DI 20 ... DI 22)
● 2030 Digital inputs/outputs, bidirectional (DI/DO 8 ... DI/DO 9)
● 2031 Digital inputs/outputs, bidirectional (DI/DO 10 ... DI/DO 11)
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Delay time = 1 to 2 current controller cycles (250 μs)
– inverted and not inverted as a binector output
– as a connector output
– Jumper open: electrically isolated.
The digital inputs function only if a reference ground is connected.
– Jumper closed, non-floating.
The reference potential of the digital inputs is the ground of the Control Unit.
Basic information about the drive system
10.5 Inputs/outputs
681