Hide thumbs Also See for Sinamics S110:
Table of Contents

Advertisement

2. Use STARTER to download project to PG:
3. Install the latest firmware version for the project.
Update the firmware and load the new project to the target device.
1. Insert the memory card containing the new firmware version into the Control Unit:
2. Go online and download the project to the target device → Copy RAM to ROM.
3. Upgrading the firmware for the DRIVE-CLiQ components takes place automatically.
4. Reset the drive unit using a POWER ON (Control Unit and all DRIVE-CLiQ components).
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
– Connect with target system (go online)
– Downloading the project into the PG
– In the project navigator, right-click Drive unit → Target device → Device version.
– For example, select version "SINAMICS S110 V4.3x" -> Change version.
– Disconnect the Control Unit from the power supply →
– Insert the memory card containing the new firmware version →
– Power up the Control Unit again.
The new firmware version is only effective in the DRIVE-CLiQ components from this point
onwards; it also appears in the version overview.
Commissioning with PROFIBUS
3.2 STARTER commissioning tool